PAS 5308 Cables  
BS5308 Part 1 / Type 1 BS5308 Part 1 / Type 2 BS5308 Part 2 / Type 1

PAS 5308 Cables

PAS 5308 Part 2

 PAS 5308 Part 2 / Type 2 (armoured cables)

       PAS 5308 Cable Part 2 Type 2 PVC-OS-SWA-PVC

Application

These cables are designed to connect electrical instrumentation and communication systems in and around process plants and similar applications. Generally used to transmit analogue or digital signals in measurement and process control where chemicals may be present. The armoured version are well adapted to underground use in industrial applications where chemical and mechanical protections are needed (refinery areas, chemical plant...).

Construction

Conductor

Annealed copper, sizes: 0.5mm² and 0.75mm² mulitistranded(Class 5), 1.5mm² and 2.5mm² multistranded(Class 2) to BS EN 60228

Insulation

PVC to BS EN 50290-2-21:2002, grade TI51

Pairing

Two insulated conductors uniformly twisted together with a lay not exceeding 100mm, Two-pair cables without individual pair screens (quads) shall have four cores laid in quad formation round a central dummy

Colour code

Multicore cables: up to 40 cores yellow with black numbers, 41 - 80 cores black with yellow numbers.  Multipair cables:See technical information

Binder tape

Non-hygroscopic binder tape of minimum thickness 0.023 mm

Collective screen

Aluminium/polyester tape is applied over the laid up pairs metallic side down in contact with tinned copper drain wire, 0.5mm²

Inner Sheath

Extruded sheath of a PVC compound conforming to BS EN 50290-2-22:2002, grade TM51

Amour

Galvanized steel wire armour

Outer sheath

Extruded sheath of a PVC compound conforming to BS EN 50290-2-22:2002, grade TM51

Sheath colour

Generally black

Electrical Properties

Temperature range: above 0˚C( fixed installation)
-15˚C to +65˚C(during operation )

Conductor Area Size

mm²

0.5

0.5

1.0

1.5

2.5

Conductor Stranding

No. x mm

1 x 0.8

16 x 0.2

1 x 1.13

7 x 0.53

7 x 0.67

Conductor resistance max

ohm/km

36.8

39.7

18.4

12.3

7.6

Insulation resistance min

Individual conductor

Gohm/km

5

5

5

5

5

individual screen

Mohm/km

1

1

1

1

1

Capacitance unbalance at 1 kHz(pair to pair screen)

pF/250m

250

Max. Mutual Capacitance @ 1 kHz for Non OS or OS cables (except one-pair and two-pairs)

pF/m

75

75

75

85

105

Max. Mutual Capacitance @ 1 kHz
IS/OS cables (include 1 pair and
2 pair)

pF/m

115

115

115

120

140

Max. L/R Ratio for adjacent cores(Inductance/Resistance)

μH/ohm

25

25

25

40

60

Test voltage

V

2000

2000

2000

2000

2000

Rated voltage

V

300/500

300/500

300/500

300/500

300/500

Parameter

Multicore

PAS 5308 Cable Part 2 Type 2 PVC-OS-SWA-PVC

Number of
Cores

Nominal Thickness of Insulation

Nominal Thickness of bedding

Nominal Diameter over Bedding

Nominal Thickness of Armour

Nominal Diameter over Armour

Nominal Thickness of Sheath

Nominal Diameter of Cable

mm

mm

mm

mm

 

mm

mm

stranded conductor 0.5 mm² (16/0.20mm)

2

0.6

0.8

6

0.9

7.8

1.3

10.4

3

0.6

0.8

6.3

0.9

8.1

1.3

10.7

4

0.6

0.8

6.9

0.9

8.7

1.3

11.3

6

0.6

0.8

8.1

0.9

9.9

1.4

12.7

10

0.6

0.9

10.4

1.25

12.9

1.5

15.9

20

0.6

1

13.5

1.25

16

1.5

19

40

0.6

1.2

18.2

1.6

21.4

1.7

24.8

80

0.6

1.4

25.1

2

29.1

1.9

32.9

stranded conductor 0.75 mm² (24/0.20mm)

2

0.6

1.3

10.8

0.8

6.4

0.9

8.2

3

0.6

1.3

11.2

0.8

6.8

0.9

8.6

4

0.6

1.4

12

0.8

7.4

0.9

9.2

6

0.6

1.4

13.5

0.9

8.9

0.9

10.7

10

0.6

1.5

17

1

11.5

1.25

14

20

0.6

1.6

20.5

1.1

14.8

1.25

17.3

40

0.6

1.7

26.5

1.3

19.9

1.6

23.1

80

0.6

2

35.5

1.5

27.5

2

31.5

stranded conductor 1.5 mm² (7/0.53mm)

2

0.6

0.8

7.3

0.9

9.1

1.4

11.9

3

0.6

0.8

7.7

0.9

9.5

1.4

12.3

4

0.6

0.9

8.7

0.9

10.5

1.4

13.3

6

0.6

0.9

10.3

1.25

12.8

1.5

15.8

10

0.6

1

13.3

1.25

15.8

1.5

18.8

20

0.6

1.2

17.4

1.6

20.6

1.7

24

40

0.6

1.4

23.4

1.6

26.6

1.8

30.2

80

0.6

1.7

32.6

2

36.6

2.1

40.8

stranded conductor 2.5 mm² (7/0.67mm)

2

0.6

0.8

8.1

0.9

9.9

1.4

12.7

3

0.6

0.9

8.8

0.9

10.6

1.4

13.4

4

0.6

0.9

9.7

0.9

11.5

1.4

14.3

6

0.6

1

11.7

1.25

14.2

1.5

17.2

10

0.6

1.1

15.1

1.6

18.3

1.6

21.5

20

0.6

1.3

19.9

1.6

23.1

1.7

26.5

40

0.6

1.5

26.7

2

30.7

2

34.7

80

0.6

1.9

37.3

2.5

42.3

2.3

46.9

Multipair

PAS 5308 Cable Part 2 Type 2 PVC-OS-SWA-PVC

Number of
Pairs

Nominal Thickness of Insulation

Nominal Thickness of bedding

Nominal Diameter over Bedding

Nominal Thickness of Armour

Nominal Diameter over Armour

Nominal Thickness of Sheath

Nominal Diameter of Cable

mm

mm

mm

mm

 

mm

mm

stranded conductor 0.5 mm² (16/0.20mm)

1

0.6

0.8

6

0.9

7.8

1.3

10.4

2

0.6

0.8

6.9

0.9

8.7

1.3

11.3

5

0.6

1

11.9

0.9

13.7

1.5

16.7

10

0.6

1.1

16.4

1.25

18.9

1.6

22.1

15

0.6

1.2

19

1.6

22.2

1.7

25.6

20

0.6

1.3

21.5

1.6

24.7

1.8

28.3

30

0.6

1.5

25.7

1.6

28.9

1.9

32.7

50

0.6

1.7

32.9

2

36.9

2.1

41.1

stranded conductor 0.75 mm² (24/0.20mm)

1

0.6

0.8

6.4

0.9

8.2

1.3

10.8

2

0.6

0.8

7.4

0.9

9.2

1.4

12

5

0.6

1

12.8

1.25

15.3

1.5

18.3

10

0.6

1.2

17.9

1.6

21.1

1.7

24.5

15

0.6

1.3

20.9

1.6

24.1

1.8

27.7

20

0.6

1.4

23.6

1.6

26.8

1.9

30.6

30

0.6

1.5

27.9

1.6

31.1

2

35.1

50

0.6

1.8

35.9

2

39.9

2.2

44.3

stranded conductor 1.5 mm² (7/0.53mm)

1

0.6

0.8

7.3

0.9

9.1

1.4

11.9

2

0.6

0.9

8.7

0.9

10.5

1.4

13.3

5

0.6

1.1

15.1

1.25

17.6

1.6

20.8

10

0.6

1.3

21.1

1.6

24.3

1.8

27.9

15

0.6

1.4

24.6

1.6

27.8

1.9

31.6

20

0.6

1.5

27.7

1.6

30.9

2

34.9

30

0.6

1.7

33

2

37

2.1

41.2

50

0.6

2.1

42.7

2.5

47.7

2.4

52.5

stranded conductor 2.5 mm² (7/0.67mm)

1

0.6

0.8

8.1

0.9

9.9

1.4

12.7

2

0.6

0.9

9.7

0.9

11.5

1.4

14.3

5

0.6

1.2

17.2

1.25

19.7

1.7

23.1

10

0.6

1.4

24.1

1.6

27.3

1.9

31.1

15

0.6

1.6

28.2

1.6

31.4

2

35.4

20

0.6

1.7

31.8

2

35.8

2.1

40

30

0.6

1.9

37.9

2

41.9

2.3

46.5

50

0.6

2.3

48.9

2.5

53.9

2.6

59.1